Switches
Track and Hold
Description While Select is set to Track (0), the value of Output will be equal to the value of Input. While Select is set to Hold (1), the value of Output will remain the same until Select is set back to Track.

The value of Output and Select are not persistent on power-down.
Availability
  • Requires library: Process Control (option -05)
  • Firmware versions 0x1021 and later
savvy-SFD Graphic trackAndHold
Graphic with Parameters trackAndHold

Parameters

Input Input, Read-write, Analog (signed 16-bit integer)
-327.67 % to 327.67 %
Select Input, Read-write, Boolean (signed 16-bit integer)
0 = Track
1 = Hold
Output Output, Read-only, Set to default on hard initialization, Analog (signed 16-bit integer)
-327.67 % to 327.67 %