Description | The value of Output will ramp to the value of Input at a rate (displayed in Rate Output) based on the Forward Up Time, Forward Down Time, Reverse Up Time, Reverse Down Time, and S Percent. Preset is available by setting Preset Enable to Active (1) and the value of Preset Value greater than 0. Setting Hold Enable to Active (1) will pause the value of Output. Reset Enable will set Output and Rate Output to 0 or Preset Value (if applicable), and has the highest priority. |
Availability |
|
savvy-SFD Graphic | |
Graphic with Parameters |
Input |
Input, Read-write, Analog (signed 16-bit integer) -327.67 % to 327.67 % |
Forward Up Time |
Internal Parameter, Read-write, Time or Rate (signed 16-bit integer) 0.1 s to 3000.0 s Minimum time for the ramp to change by 100% when the input is positive and moving away from zero. |
Forward Down Time |
Internal Parameter, Read-write, Time or Rate (signed 16-bit integer) 0.1 s to 3000.0 s Minimum time for the ramp to change by 100% when the output is positive and moving toward zero. |
Reverse Down Time |
Internal Parameter, Read-write, Time or Rate (signed 16-bit integer) 0.1 s to 3000.0 s Minimum time for the ramp to change by 100% when the output is negative and moving toward zero. |
Reverse Up Time |
Internal Parameter, Read-write, Time or Rate (signed 16-bit integer) 0.1 s to 3000.0 s Minimum time for the ramp to change by 100% when the output is negative and moving away from zero. |
S Percent |
Internal Parameter, Read-write, Analog (signed 16-bit integer) 0.01 % to 100.00 % Specifies how much of the ramp time will be spent in the S part of the curve. 0% means a linear ramp, 100% means all S. Note that increasing the S Percent will increase the maximum rate of change of the ramp. |
Hold Enable |
Input, Read-write, Boolean (signed 16-bit integer) Immediately holds the ramp at its current value. Hold Enable simply suspends processing of the ramp. 0 = Inactive 1 = Hold |
Reset Enable |
Input, Read-write, Boolean (signed 16-bit integer) Immediately sets the output to zero and resets the S calculations 0 = Inactive 1 = Reset |
Preset Enable |
Input, Read-write, Boolean (signed 16-bit integer) Immediately sets the ramp output to Preset Value and resets the S calculations 0 = Inactive 1 = Preset |
Preset Value |
Input, Read-write, Analog (signed 16-bit integer) -327.67 % to 327.67 % |
Output |
Output, Read-only, Analog (signed 16-bit integer) -327.67 % to 327.67 % |
Rate Output |
Output, Read-only, Analog (signed 16-bit integer) -3276.7 %/s to 3276.7 %/s |