ModbusRTU Master
Modbus Master Stats
Description (description coming soon)
Availability
  • Available only in the dw2xx & dw2xx-v2 series products
  • Requires library: System & I/O
  • Requires: Modbus Master
  • Singleton function block
  • Firmware versions 0x2011 and later
savvy-SFD Graphic mbmStats
Graphic with Parameters mbmStats

Parameters

Function Block Transactions Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Savvy Transactions Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
CommsServer Transactions Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535

ModbusRTU Slave, ModbusTCP Slave and EIP/PCCC Server
Incoming Conn Transactions Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Outgoing Conn Transactions Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Background Transactions Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Timeout Errors Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Runt Response Errors Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Address Mismatch Errors Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
CRC Errors Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
FC Mismatch Errors Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Unknown FC Errors Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Length Errors Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Byte Count Errors Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Unknown Errors Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Comms Parity Errors Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Comms Framing Errors Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Comms Overrun Errors Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Comms Break Errors Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Comms Multiple Errors Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Unexpected Response Errors Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Illegal Function Exceptions Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Illegal Data Address Exceptions Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Illegal Data Value Exceptions Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Slave Failure Exceptions Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Slave Busy Exceptions Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Other Exceptions Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Last Error Output, Read-write, Enumerated (signed 16-bit integer)
-16 = Unexpected Response
-15 = Multiple Errors (parity, framing, overrun, or break)
-14 = Break Received
-13 = Overrun Error
-12 = Framing Error
-11 = Parity Error
-10 = Unknown Error
-9 = Unexpected Byte Count
-8 = Unexpected Length
-7 = Internal Error
-6 = Unexpected Function Code
-5 = CRC Failure
-4 = Unexpected Address
-3 = Runt Response
-2 = Timeout
-1 = No Comms Port Defined
0 = None
1 = Illegal Function
2 = Illegal Data Address
3 = Illegal Data Value
4 = Slave Device Failure
5 = Acknowledge
6 = Slave Device Busy
7 = Negative Acknowledge
8 = Memory Parity Error
33 = Data Out of Range
34 = Write Protected
35 = Write during Undervoltage
36 = Write during Parameter Processing
Last Error Function Code Internal Parameter, Read-only, Set to default on hard initialization, Hexadecimal (unsigned 16-bit integer)
0x0 to 0xFFFF
Last Error Address Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0 to 65535
Last Error Agent Internal Parameter, Read-only, Set to default on hard initialization, Enumerated (unsigned 16-bit integer)
0 = None
1 = Function Block
2 = Function Block (Wait)
3 = Savvy
4 = Modbus Slave
5 = Incoming Connection
6 = Outgoing Connection
7 = Background
8 = EIP/PCCC Server
Outconn Sample Delay Internal Parameter, Read-only, Set to default on hard initialization, Analog (unsigned 16-bit integer)
0.0 ms to 13107.0 ms
65535 = Overrange