I/O (FI)
FI3 Counter Input
Description Set the Input Type to define the threshold Voltage to set output HIGH (1) and the Direction.

Outputs are the pulse count as a Count type parameter and the signal frequency and direction as a Floating Point type parameter.
Availability
  • Available only in the dw2xx-v2 series products
  • Requires library: System & I/O
  • Requires: Four Frequency Inputs
  • Singleton function block
  • Firmware versions 0x2105 and later
savvy-SFD Graphic fin3c
Graphic with Parameters fin3c

Parameters

Input Type Internal Parameter, Read-write, Enumerated (signed 16-bit integer)
0 = 5V Logic with pull-down
1 = 5V Logic with pull-up
2 = 5V Logic
3 = 24V Logic with pull-down
Count+ Output, Read-only, Placeholder (special (count & timestamp))
2 = FI 3
Filter Size Internal Parameter, Read-write, Enumerated (signed 16-bit integer)

This is the sample size for the filter. A larger size provides more filtering and a slower response. Note that large filter sizes can be very slow - e.g. 4096 @ 5ms timebase is over 20 seconds.
1 = 1
2 = 2
3 = 4
4 = 8
5 = 16
6 = 32
7 = 64
8 = 128
9 = 256
10 = 512
11 = 1024
12 = 2048
13 = 4096
Freq+Dir Output, Read-only, Analog (32-bit IEEE-754 floating point value)
-4000.000 kHz to 4000.000 kHz
Direction Input, Read-write, Boolean (signed 16-bit integer)
0 = Forward
1 = Reverse