Description | Set the Input Type to define the threshold Voltage to set output HIGH (1) and the Direction. Outputs are the pulse count as a Count type parameter and the signal frequency and direction as a Floating Point type parameter. |
Availability |
|
savvy-SFD Graphic | |
Graphic with Parameters |
Input Type |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) 0 = 5V Logic with pull-down 1 = 5V Logic with pull-up 2 = 5V Logic 3 = 24V Logic with pull-down |
Count+ |
Output, Read-only, Placeholder (special (count & timestamp)) 2 = FI 3 |
Filter Size |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) This is the sample size for the filter. A larger size provides more filtering and a slower response. Note that large filter sizes can be very slow - e.g. 4096 @ 5ms timebase is over 20 seconds. 1 = 1 2 = 2 3 = 4 4 = 8 5 = 16 6 = 32 7 = 64 8 = 128 9 = 256 10 = 512 11 = 1024 12 = 2048 13 = 4096 |
Freq+Dir |
Output, Read-only, Analog (32-bit IEEE-754 floating point value) -4000.000 kHz to 4000.000 kHz |
Direction |
Input, Read-write, Boolean (signed 16-bit integer) 0 = Forward 1 = Reverse |