Time Counters
DeciHours Counter
Description While Run Enable is set to Run (1) and Present Enable is Inactive (0), Seconds will display the time elapsed in seconds, and Hours Elapsed will display the time elapsed in whole number of hours.

If a preset number of hours is needed, set the value in Preset Hours and then set Preset Enable to Active (1), and then Inactive (0). Hours Elapsed will be set to the value of Preset Hours.
Availability
  • Available only in the dw2xx & dw2xx-v2 series products
  • Requires library: Process Control (option -05)
  • Firmware versions 0x2001 and later
savvy-SFD Graphic dHoursCounter
Graphic with Parameters dHoursCounter

Parameters

Hours Elapsed Output, Read-only, Analog (signed 16-bit integer)
0.0 h to 3276.7 h
32767 = overflow
Run Enable Input, Read-write, Boolean (signed 16-bit integer)
0 = Stop
1 = Run
Preset Enable Input, Read-write, Boolean (signed 16-bit integer)
0 = Inactive
1 = Preset
Preset Hours Input, Read-write, Analog (signed 16-bit integer)
0.0 h to 3276.6 h
Seconds Internal Parameter, Read-only, Analog (unsigned 16-bit integer)
0 s to 359 s