Description | The System function block contains information about the function block engine. Also included are statically-bound parameters such as those associated with Modbus. |
Availability |
|
savvy-SFD Graphic | |
Graphic with Parameters |
Power Status |
Internal Parameter, Read-only, Analog (signed 16-bit integer) -0.0 V to 32.8 V Either the actual supply voltage or the supply voltage status (depending on whether universal inputs are fitted). Unsupported on the dwM3. -1 = Not Available 0 = Fail 1 = OK |
Timebase Setpoint |
Internal Parameter, Read-only, Analog (signed 16-bit integer) 3 ms to 10000 ms Desired cycle time. It is recommended that the this parameter be set approximately 15ms longer than the execute time (normally 30ms or greater). |
Timebase Measured |
Internal Parameter, Read-only, Analog (signed 16-bit integer) 0 ms to 32767 ms Unfiltered cycle time. This includes the FBE execution time and the overhead (e.g. I/O Modbus, etc.) |
Execute Time |
Internal Parameter, Read-only, Analog (signed 16-bit integer) 0 ms to 32767 ms Unfiltered execute time. This is the FBE execution time ignoring overhead. 0 = <1 ms |
Program Line Number |
Internal Parameter, Read-only, Analog (signed 16-bit integer) 0 to 512 Length of program or line at which load error occurred |
Program Status |
Internal Parameter, Read-only, Enumerated (signed 16-bit integer) -2 = Timebase Overrun -1 = Phantom 0 = Unterminated Program 1 = OK 2 = Unknown Type 3 = Unknown Function Block 4 = Parameter Out of Range 5 = Already has an Incoming 6 = Outgoing Out Of Range 7 = Incoming Out Of Range 8 = Incoming Already Used 9 = Outgoing Phase Error 10 = Outgoing Already Used 11 = Parameter Not Bound 12 = Outgoing Not Allowed 13 = Incoming Not Allowed 14 = Function Block Collision 15 = Function Block Outside Capability 16 = Function Block Not Owned 17 = System Block Error 18 = Resource Conflict 19 = Associated FB is Wrong Type 20 = Associated FB Must be Defined 21 = Parameter Data Out Of Range 22 = Timebase Too Long 23 = Associated FB is Misaligned 24 = Out of Pool Memory 25 = Unknown Initialization Mode 26 = Invalid Capabilities 27 = Singleton Conflict 28 = Incompatible Function Block 29 = Resource Not Present 30 = Too Many Modbus Registers |
Logging Detail |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) 0 = Normal 4096 = Verbose 8192 = Debug |
Ethernet Overruns |
Internal Parameter, Read-only, Analog (unsigned 16-bit integer) 0 to 32767 0 = None |
Modbus Slave Indirect 0 |
Internal Parameter, Read-write, Analog (unsigned 16-bit integer) 0 to 65535 |
Modbus Slave Indirect 1 |
Internal Parameter, Read-write, Analog (unsigned 16-bit integer) 0 to 65535 |
Modbus Slave Indirect 2 |
Internal Parameter, Read-write, Analog (unsigned 16-bit integer) 0 to 65535 |
Modbus Slave Indirect 3 |
Internal Parameter, Read-write, Analog (unsigned 16-bit integer) 0 to 65535 |
Modbus Slave Indirect 4 |
Internal Parameter, Read-write, Analog (unsigned 16-bit integer) 0 to 65535 |
Modbus Slave Indirect 5 |
Internal Parameter, Read-write, Analog (unsigned 16-bit integer) 0 to 65535 |
Modbus Slave Indirect 6 |
Internal Parameter, Read-write, Analog (unsigned 16-bit integer) 0 to 65535 |
Modbus Slave Indirect 7 |
Internal Parameter, Read-write, Analog (unsigned 16-bit integer) 0 to 65535 |
ModbusTCP Slave Port |
Internal Parameter, Read-write, Analog (unsigned 16-bit integer) 1 to 49151 502 = Standard (502) |
ModbusRTU Slave Speed |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) 50 = 50 b/s 75 = 75 b/s 110 = 110 b/s 150 = 150 b/s 300 = 300 b/s 600 = 600 b/s 1200 = 1200 b/s 2400 = 2400 b/s 4800 = 4800 b/s 7200 = 7200 b/s 9600 = 9600 b/s 14400 = 14.4 kb/s 19200 = 19.2 kb/s |
ModbusRTU Slave Address |
Internal Parameter, Read-write, Analog (signed 16-bit integer) 1 to 247 |
UIP1 FIR Filter Size |
Internal Parameter, Read-write, Analog (unsigned 16-bit integer) 1 to 16 |
UIP2 FIR Filter Size |
Internal Parameter, Read-write, Analog (unsigned 16-bit integer) 1 to 16 |
UIP3 FIR Filter Size |
Internal Parameter, Read-write, Analog (unsigned 16-bit integer) 1 to 16 |
UIP4 FIR Filter Size |
Internal Parameter, Read-write, Analog (unsigned 16-bit integer) 1 to 16 |
UIP5 FIR Filter Size |
Internal Parameter, Read-write, Analog (unsigned 16-bit integer) 1 to 16 |
UIP6 FIR Filter Size |
Internal Parameter, Read-write, Analog (unsigned 16-bit integer) 1 to 16 |
UIP7 FIR Filter Size |
Internal Parameter, Read-write, Analog (unsigned 16-bit integer) 1 to 16 |