ModbusRTU Master
Optidrive Plus
Description (description coming soon)
Availability
  • Available only in the dw1xx series products
  • Requires library: System & I/O
  • Requires: Generic ModbusRTU Master Unisolated EIA-485 (option -13) or Generic ModbusRTU Master Isolated EIA-485 (option -12)
  • Firmware versions 0x1032 and later
savvy-SFD Graphic modbusOptidriveODP
Graphic with Parameters modbusOptidriveODP

Parameters

Modbus Address Internal Parameter, Read-write, Analog (signed 16-bit integer)
1 to 247
Command Input, Read-write, Enumerated (signed 16-bit integer)
0 = Stop
1 = Start
2 = Reset
4 = Stop with Second Ramp
Command Last Error Internal Parameter, Read-write, Enumerated (signed 16-bit integer)
-2 = Timeout
-1 = No Comms Port Defined
0 = None
1 = Illegal Function
2 = Illegal Data Address
3 = Illegal Data Value
4 = Slave Device Failure
5 = Acknowledge
6 = Slave Device Busy
7 = Negative Acknowledge
8 = Memory Parity Error
33 = Data Out of Range
34 = Write Protected
35 = Write during Undervoltage
36 = Write during Parameter Processing
64 = Comms Overrun Error
65 = Comms CRC Error
66 = Comms Address Error
67 = Comms Response Length Error
68 = Comms General Error
69 = Comms Unexpected Response
70 = Comms Buffer Overflow
72 = Comms Parity Error
73 = Comms No Buffer Available
Command Enable Internal Parameter, Read-write, Boolean (signed 16-bit integer)
0 = Disable
1 = Enable
Speed Reference Input, Read-write, Analog (signed 16-bit integer)
-120.0 Hz to 120.0 Hz
Speed Ref Last Error Internal Parameter, Read-write, Enumerated (signed 16-bit integer)
-2 = Timeout
-1 = No Comms Port Defined
0 = None
1 = Illegal Function
2 = Illegal Data Address
3 = Illegal Data Value
4 = Slave Device Failure
5 = Acknowledge
6 = Slave Device Busy
7 = Negative Acknowledge
8 = Memory Parity Error
33 = Data Out of Range
34 = Write Protected
35 = Write during Undervoltage
36 = Write during Parameter Processing
64 = Comms Overrun Error
65 = Comms CRC Error
66 = Comms Address Error
67 = Comms Response Length Error
68 = Comms General Error
69 = Comms Unexpected Response
70 = Comms Buffer Overflow
72 = Comms Parity Error
73 = Comms No Buffer Available
Speed Ref Enable Internal Parameter, Read-write, Boolean (signed 16-bit integer)
0 = Disable
1 = Enable
Acceleration Ramp Time Input, Read-write, Analog (signed 16-bit integer)
0.0 s to 3000.0 s
Acc Ramp Last Error Internal Parameter, Read-write, Enumerated (signed 16-bit integer)
-2 = Timeout
-1 = No Comms Port Defined
0 = None
1 = Illegal Function
2 = Illegal Data Address
3 = Illegal Data Value
4 = Slave Device Failure
5 = Acknowledge
6 = Slave Device Busy
7 = Negative Acknowledge
8 = Memory Parity Error
33 = Data Out of Range
34 = Write Protected
35 = Write during Undervoltage
36 = Write during Parameter Processing
64 = Comms Overrun Error
65 = Comms CRC Error
66 = Comms Address Error
67 = Comms Response Length Error
68 = Comms General Error
69 = Comms Unexpected Response
70 = Comms Buffer Overflow
72 = Comms Parity Error
73 = Comms No Buffer Available
Acc Ramp Enable Internal Parameter, Read-write, Boolean (signed 16-bit integer)
0 = Disable
1 = Enable
Drive Status Output, Read-only, Enumerated (signed 16-bit integer)
0 = Stopped
1 = Running
258 = Brake Overcurrent Trip
514 = Overcurrent Trip
770 = External Trip
1026 = Overvoltage Trip
1282 = Undervoltage Trip
1538 = Overtemp Trip
1794 = Undertemp Trip
2050 = Spin Start Fault
2306 = Default Parameters Loaded
2562 = Overload Trip
2818 = Phase Imbalance Trip
3074 = Brake Resistor Overload Trip
3330 = Power Stage Trip
3586 = Comms Link Loss Trip
3842 = Phase Loss Trip
4098 = Thermistor Trip
4354 = Autotune Fault
5122 = Encoder Fault 00
Status Last Error Internal Parameter, Read-write, Enumerated (signed 16-bit integer)
-2 = Timeout
-1 = No Comms Port Defined
0 = None
1 = Illegal Function
2 = Illegal Data Address
3 = Illegal Data Value
4 = Slave Device Failure
5 = Acknowledge
6 = Slave Device Busy
7 = Negative Acknowledge
8 = Memory Parity Error
33 = Data Out of Range
34 = Write Protected
35 = Write during Undervoltage
36 = Write during Parameter Processing
64 = Comms Overrun Error
65 = Comms CRC Error
66 = Comms Address Error
67 = Comms Response Length Error
68 = Comms General Error
69 = Comms Unexpected Response
70 = Comms Buffer Overflow
72 = Comms Parity Error
73 = Comms No Buffer Available
Status Enable Internal Parameter, Read-write, Boolean (signed 16-bit integer)
0 = Disable
1 = Enable
Motor Speed Output, Read-only, Analog (signed 16-bit integer)
-3000.0 Hz to 3000.0 Hz
Motor Speed Last Error Internal Parameter, Read-write, Enumerated (signed 16-bit integer)
-2 = Timeout
-1 = No Comms Port Defined
0 = None
1 = Illegal Function
2 = Illegal Data Address
3 = Illegal Data Value
4 = Slave Device Failure
5 = Acknowledge
6 = Slave Device Busy
7 = Negative Acknowledge
8 = Memory Parity Error
33 = Data Out of Range
34 = Write Protected
35 = Write during Undervoltage
36 = Write during Parameter Processing
64 = Comms Overrun Error
65 = Comms CRC Error
66 = Comms Address Error
67 = Comms Response Length Error
68 = Comms General Error
69 = Comms Unexpected Response
70 = Comms Buffer Overflow
72 = Comms Parity Error
73 = Comms No Buffer Available
Motor Speed Enable Internal Parameter, Read-write, Boolean (signed 16-bit integer)
0 = Disable
1 = Enable
Motor Current Output, Read-only, Analog (signed 16-bit integer)
-3000.0 A to 3000.0 A
Motor Current Last Error Internal Parameter, Read-write, Enumerated (signed 16-bit integer)
-2 = Timeout
-1 = No Comms Port Defined
0 = None
1 = Illegal Function
2 = Illegal Data Address
3 = Illegal Data Value
4 = Slave Device Failure
5 = Acknowledge
6 = Slave Device Busy
7 = Negative Acknowledge
8 = Memory Parity Error
33 = Data Out of Range
34 = Write Protected
35 = Write during Undervoltage
36 = Write during Parameter Processing
64 = Comms Overrun Error
65 = Comms CRC Error
66 = Comms Address Error
67 = Comms Response Length Error
68 = Comms General Error
69 = Comms Unexpected Response
70 = Comms Buffer Overflow
72 = Comms Parity Error
73 = Comms No Buffer Available
Motor Current Enable Internal Parameter, Read-write, Boolean (signed 16-bit integer)
0 = Disable
1 = Enable
Motor Power Output, Read-only, Analog (signed 16-bit integer)
-300.00 to 300.00

The units of Motor Power may be kW or HP depending on the drive model.
Motor Power Last Error Internal Parameter, Read-write, Enumerated (signed 16-bit integer)
-2 = Timeout
-1 = No Comms Port Defined
0 = None
1 = Illegal Function
2 = Illegal Data Address
3 = Illegal Data Value
4 = Slave Device Failure
5 = Acknowledge
6 = Slave Device Busy
7 = Negative Acknowledge
8 = Memory Parity Error
33 = Data Out of Range
34 = Write Protected
35 = Write during Undervoltage
36 = Write during Parameter Processing
64 = Comms Overrun Error
65 = Comms CRC Error
66 = Comms Address Error
67 = Comms Response Length Error
68 = Comms General Error
69 = Comms Unexpected Response
70 = Comms Buffer Overflow
72 = Comms Parity Error
73 = Comms No Buffer Available
Motor Power Enable Internal Parameter, Read-write, Boolean (signed 16-bit integer)
0 = Disable
1 = Enable
Deceleration Ramp Time Input, Read-write, Analog (signed 16-bit integer)
0.0 s to 3000.0 s
0 = Dynamic Fast Ramp
Decel Ramp Last Error Internal Parameter, Read-write, Enumerated (signed 16-bit integer)
-2 = Timeout
-1 = No Comms Port Defined
0 = None
1 = Illegal Function
2 = Illegal Data Address
3 = Illegal Data Value
4 = Slave Device Failure
5 = Acknowledge
6 = Slave Device Busy
7 = Negative Acknowledge
8 = Memory Parity Error
33 = Data Out of Range
34 = Write Protected
35 = Write during Undervoltage
36 = Write during Parameter Processing
64 = Comms Overrun Error
65 = Comms CRC Error
66 = Comms Address Error
67 = Comms Response Length Error
68 = Comms General Error
69 = Comms Unexpected Response
70 = Comms Buffer Overflow
72 = Comms Parity Error
73 = Comms No Buffer Available
Decel Ramp Enable Internal Parameter, Read-write, Boolean (signed 16-bit integer)
0 = Disable
1 = Enable
Modbus Address Internal Parameter, Read-write, Analog (signed 16-bit integer)
1 to 247
Digital Input Status Output, Read-only, Bitfield (signed 16-bit integer)
0 = Digital Input 1
1 = Digital Input 2
2 = Digital Input 3
3 = Digital Input 4
Digital Inputs Last Error Internal Parameter, Read-write, Enumerated (signed 16-bit integer)
-2 = Timeout
-1 = No Comms Port Defined
0 = None
1 = Illegal Function
2 = Illegal Data Address
3 = Illegal Data Value
4 = Slave Device Failure
5 = Acknowledge
6 = Slave Device Busy
7 = Negative Acknowledge
8 = Memory Parity Error
33 = Data Out of Range
34 = Write Protected
35 = Write during Undervoltage
36 = Write during Parameter Processing
64 = Comms Overrun Error
65 = Comms CRC Error
66 = Comms Address Error
67 = Comms Response Length Error
68 = Comms General Error
69 = Comms Unexpected Response
70 = Comms Buffer Overflow
72 = Comms Parity Error
73 = Comms No Buffer Available
Digital Inputs Enable Internal Parameter, Read-write, Boolean (signed 16-bit integer)
0 = Disable
1 = Enable