Description | (description coming soon) |
Availability |
|
savvy-SFD Graphic | |
Graphic with Parameters |
Modbus Address |
Internal Parameter, Read-write, Analog (signed 16-bit integer) 1 to 247 |
Command |
Input, Read-write, Enumerated (signed 16-bit integer) 0 = Stop 1 = Start 2 = Reset 4 = Stop with Second Ramp |
Command Last Error |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) -16 = Unexpected Response -15 = Multiple Errors (parity, framing, overrun, or break) -14 = Break Received -13 = Overrun Error -12 = Framing Error -11 = Parity Error -10 = Unknown Error -9 = Unexpected Byte Count -8 = Unexpected Length -7 = Internal Error -6 = Unexpected Function Code -5 = CRC Failure -4 = Unexpected Address -3 = Runt Response -2 = Timeout -1 = No Comms Port Defined 0 = None 1 = Illegal Function 2 = Illegal Data Address 3 = Illegal Data Value 4 = Slave Device Failure 5 = Acknowledge 6 = Slave Device Busy 7 = Negative Acknowledge 8 = Memory Parity Error 33 = Data Out of Range 34 = Write Protected 35 = Write during Undervoltage 36 = Write during Parameter Processing |
Command Enable |
Internal Parameter, Read-write, Boolean (signed 16-bit integer) 0 = Disable 1 = Enable |
Command Priority |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) 0 = Low 1 = Medium 2 = High |
Speed Reference |
Input, Read-write, Analog (signed 16-bit integer) -120.0 Hz to 120.0 Hz |
Speed Ref Last Error |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) -16 = Unexpected Response -15 = Multiple Errors (parity, framing, overrun, or break) -14 = Break Received -13 = Overrun Error -12 = Framing Error -11 = Parity Error -10 = Unknown Error -9 = Unexpected Byte Count -8 = Unexpected Length -7 = Internal Error -6 = Unexpected Function Code -5 = CRC Failure -4 = Unexpected Address -3 = Runt Response -2 = Timeout -1 = No Comms Port Defined 0 = None 1 = Illegal Function 2 = Illegal Data Address 3 = Illegal Data Value 4 = Slave Device Failure 5 = Acknowledge 6 = Slave Device Busy 7 = Negative Acknowledge 8 = Memory Parity Error 33 = Data Out of Range 34 = Write Protected 35 = Write during Undervoltage 36 = Write during Parameter Processing |
Speed Ref Enable |
Internal Parameter, Read-write, Boolean (signed 16-bit integer) 0 = Disable 1 = Enable |
Speed Ref Priority |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) 0 = Low 1 = Medium 2 = High |
Acceleration Ramp Time |
Input, Read-write, Analog (signed 16-bit integer) 0.0 s to 3000.0 s |
Acc Ramp Last Error |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) -16 = Unexpected Response -15 = Multiple Errors (parity, framing, overrun, or break) -14 = Break Received -13 = Overrun Error -12 = Framing Error -11 = Parity Error -10 = Unknown Error -9 = Unexpected Byte Count -8 = Unexpected Length -7 = Internal Error -6 = Unexpected Function Code -5 = CRC Failure -4 = Unexpected Address -3 = Runt Response -2 = Timeout -1 = No Comms Port Defined 0 = None 1 = Illegal Function 2 = Illegal Data Address 3 = Illegal Data Value 4 = Slave Device Failure 5 = Acknowledge 6 = Slave Device Busy 7 = Negative Acknowledge 8 = Memory Parity Error 33 = Data Out of Range 34 = Write Protected 35 = Write during Undervoltage 36 = Write during Parameter Processing |
Acc Ramp Enable |
Internal Parameter, Read-write, Boolean (signed 16-bit integer) 0 = Disable 1 = Enable |
Acc Ramp Priority |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) 0 = Low 1 = Medium 2 = High |
Drive Status |
Output, Read-only, Enumerated (signed 16-bit integer) 0 = Stopped 1 = Running 258 = Brake Overcurrent Trip 514 = Overcurrent Trip 770 = External Trip 1026 = Overvoltage Trip 1282 = Undervoltage Trip 1538 = Overtemp Trip 1794 = Undertemp Trip 2050 = Spin Start Fault 2306 = Default Parameters Loaded 2562 = Overload Trip 2818 = Phase Imbalance Trip 3074 = Brake Resistor Overload Trip 3330 = Power Stage Trip 3586 = Comms Link Loss Trip 3842 = Phase Loss Trip 4098 = Thermistor Trip 4354 = Autotune Fault 5122 = Encoder Fault 00 |
Status Last Error |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) -16 = Unexpected Response -15 = Multiple Errors (parity, framing, overrun, or break) -14 = Break Received -13 = Overrun Error -12 = Framing Error -11 = Parity Error -10 = Unknown Error -9 = Unexpected Byte Count -8 = Unexpected Length -7 = Internal Error -6 = Unexpected Function Code -5 = CRC Failure -4 = Unexpected Address -3 = Runt Response -2 = Timeout -1 = No Comms Port Defined 0 = None 1 = Illegal Function 2 = Illegal Data Address 3 = Illegal Data Value 4 = Slave Device Failure 5 = Acknowledge 6 = Slave Device Busy 7 = Negative Acknowledge 8 = Memory Parity Error 33 = Data Out of Range 34 = Write Protected 35 = Write during Undervoltage 36 = Write during Parameter Processing |
Status Enable |
Internal Parameter, Read-write, Boolean (signed 16-bit integer) 0 = Disable 1 = Enable |
Status Priority |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) 0 = Low 1 = Medium 2 = High |
Motor Speed |
Output, Read-only, Analog (signed 16-bit integer) -3000.0 Hz to 3000.0 Hz |
Motor Speed Last Error |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) -16 = Unexpected Response -15 = Multiple Errors (parity, framing, overrun, or break) -14 = Break Received -13 = Overrun Error -12 = Framing Error -11 = Parity Error -10 = Unknown Error -9 = Unexpected Byte Count -8 = Unexpected Length -7 = Internal Error -6 = Unexpected Function Code -5 = CRC Failure -4 = Unexpected Address -3 = Runt Response -2 = Timeout -1 = No Comms Port Defined 0 = None 1 = Illegal Function 2 = Illegal Data Address 3 = Illegal Data Value 4 = Slave Device Failure 5 = Acknowledge 6 = Slave Device Busy 7 = Negative Acknowledge 8 = Memory Parity Error 33 = Data Out of Range 34 = Write Protected 35 = Write during Undervoltage 36 = Write during Parameter Processing |
Motor Speed Enable |
Internal Parameter, Read-write, Boolean (signed 16-bit integer) 0 = Disable 1 = Enable |
Motor Speed Priority |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) 0 = Low 1 = Medium 2 = High |
Motor Current |
Output, Read-only, Analog (signed 16-bit integer) -3000.0 A to 3000.0 A |
Motor Current Last Error |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) -16 = Unexpected Response -15 = Multiple Errors (parity, framing, overrun, or break) -14 = Break Received -13 = Overrun Error -12 = Framing Error -11 = Parity Error -10 = Unknown Error -9 = Unexpected Byte Count -8 = Unexpected Length -7 = Internal Error -6 = Unexpected Function Code -5 = CRC Failure -4 = Unexpected Address -3 = Runt Response -2 = Timeout -1 = No Comms Port Defined 0 = None 1 = Illegal Function 2 = Illegal Data Address 3 = Illegal Data Value 4 = Slave Device Failure 5 = Acknowledge 6 = Slave Device Busy 7 = Negative Acknowledge 8 = Memory Parity Error 33 = Data Out of Range 34 = Write Protected 35 = Write during Undervoltage 36 = Write during Parameter Processing |
Motor Current Enable |
Internal Parameter, Read-write, Boolean (signed 16-bit integer) 0 = Disable 1 = Enable |
Motor Current Priority |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) 0 = Low 1 = Medium 2 = High |
Motor Power |
Output, Read-only, Analog (signed 16-bit integer) -300.00 to 300.00 The units of Motor Power may be kW or HP depending on the drive model. |
Motor Power Last Error |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) -16 = Unexpected Response -15 = Multiple Errors (parity, framing, overrun, or break) -14 = Break Received -13 = Overrun Error -12 = Framing Error -11 = Parity Error -10 = Unknown Error -9 = Unexpected Byte Count -8 = Unexpected Length -7 = Internal Error -6 = Unexpected Function Code -5 = CRC Failure -4 = Unexpected Address -3 = Runt Response -2 = Timeout -1 = No Comms Port Defined 0 = None 1 = Illegal Function 2 = Illegal Data Address 3 = Illegal Data Value 4 = Slave Device Failure 5 = Acknowledge 6 = Slave Device Busy 7 = Negative Acknowledge 8 = Memory Parity Error 33 = Data Out of Range 34 = Write Protected 35 = Write during Undervoltage 36 = Write during Parameter Processing |
Motor Power Enable |
Internal Parameter, Read-write, Boolean (signed 16-bit integer) 0 = Disable 1 = Enable |
Motor Power Priority |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) 0 = Low 1 = Medium 2 = High |
Deceleration Ramp Time |
Input, Read-write, Analog (signed 16-bit integer) 0.0 s to 3000.0 s 0 = Dynamic Fast Ramp |
Decel Ramp Last Error |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) -16 = Unexpected Response -15 = Multiple Errors (parity, framing, overrun, or break) -14 = Break Received -13 = Overrun Error -12 = Framing Error -11 = Parity Error -10 = Unknown Error -9 = Unexpected Byte Count -8 = Unexpected Length -7 = Internal Error -6 = Unexpected Function Code -5 = CRC Failure -4 = Unexpected Address -3 = Runt Response -2 = Timeout -1 = No Comms Port Defined 0 = None 1 = Illegal Function 2 = Illegal Data Address 3 = Illegal Data Value 4 = Slave Device Failure 5 = Acknowledge 6 = Slave Device Busy 7 = Negative Acknowledge 8 = Memory Parity Error 33 = Data Out of Range 34 = Write Protected 35 = Write during Undervoltage 36 = Write during Parameter Processing |
Decel Ramp Enable |
Internal Parameter, Read-write, Boolean (signed 16-bit integer) 0 = Disable 1 = Enable |
Decel Ramp Priority |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) 0 = Low 1 = Medium 2 = High |
Modbus Address |
Internal Parameter, Read-write, Analog (signed 16-bit integer) 1 to 247 |
Digital Input Status |
Output, Read-only, Bitfield (signed 16-bit integer) 0 = Digital Input 1 1 = Digital Input 2 2 = Digital Input 3 3 = Digital Input 4 |
Digital Inputs Last Error |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) -16 = Unexpected Response -15 = Multiple Errors (parity, framing, overrun, or break) -14 = Break Received -13 = Overrun Error -12 = Framing Error -11 = Parity Error -10 = Unknown Error -9 = Unexpected Byte Count -8 = Unexpected Length -7 = Internal Error -6 = Unexpected Function Code -5 = CRC Failure -4 = Unexpected Address -3 = Runt Response -2 = Timeout -1 = No Comms Port Defined 0 = None 1 = Illegal Function 2 = Illegal Data Address 3 = Illegal Data Value 4 = Slave Device Failure 5 = Acknowledge 6 = Slave Device Busy 7 = Negative Acknowledge 8 = Memory Parity Error 33 = Data Out of Range 34 = Write Protected 35 = Write during Undervoltage 36 = Write during Parameter Processing |
Digital Inputs Enable |
Internal Parameter, Read-write, Boolean (signed 16-bit integer) 0 = Disable 1 = Enable |
Digital Inputs Priority |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) 0 = Low 1 = Medium 2 = High |