Description | (description coming soon) |
Availability |
|
savvy-SFD Graphic | |
Graphic with Parameters |
Channel 1 Source |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) 0 = T3 Input 1 = T4 Input 2 = T5 I/O |
Channel 1 Pulses Per Revolution |
Input, Read-write, Analog (signed 16-bit integer) 1 ppr to 30000 ppr |
Channel 1 Speed |
Internal Parameter, Read-only, Analog (signed 16-bit integer) -32767 RPM to 32767 RPM |
Channel 1 Multiplier |
Input, Read-write, Analog (signed 16-bit integer) -3.2767 to 3.2767 |
Channel 1 Divider |
Input, Read-write, Analog (signed 16-bit integer) 0.0001 to 3.2767 |
Channel 2 Source |
Internal Parameter, Read-write, Enumerated (signed 16-bit integer) 0 = T3 Input 1 = T4 Input 2 = T5 I/O |
Channel 2 Pulses Per Revolution |
Input, Read-write, Analog (signed 16-bit integer) 1 ppr to 30000 ppr |
Channel 2 Speed |
Internal Parameter, Read-only, Analog (signed 16-bit integer) -32767 RPM to 32767 RPM |
Channel 2 Multiplier |
Input, Read-write, Analog (signed 16-bit integer) -3.2767 to 3.2767 |
Channel 2 Divider |
Input, Read-write, Analog (signed 16-bit integer) 0.0001 to 3.2767 |
Reset |
Input, Read-write, Boolean (signed 16-bit integer) 0 = Inactive 1 = Reset |
Upper Clamp |
Input, Read-write, Analog (signed 16-bit integer) 0.0000 revs to 3.2767 revs If the Input exceeds this value, the Output will be set to this value. |
Lower Clamp |
Input, Read-write, Analog (signed 16-bit integer) -3.2767 revs to 0.0000 revs If the Input is less than this value, the Output will be set to this value. |
Clamping Output |
Output, Read-only, Boolean (signed 16-bit integer) 0 = Not Clamping 1 = Clamping |
Output |
Output, Read-only, Analog (signed 16-bit integer) -3.2767 revs to 3.2767 revs -32767 = - overrange 32767 = + overrange |