Description | To use this function block, write to the input parameter. The timer is reset whenever a non-zero value is received. If the remote device fails or is powered down or if the network fails, the timer will timeout and the output will go true. |
Availability |
|
savvy-SFD Graphic | |
Graphic with Parameters |
Input |
Input, Read-write, Placeholder (signed 16-bit integer) The timer is reset whenever a non-zero value is written. |
Timer |
Internal Parameter, Read-only, Analog (unsigned 16-bit integer) 0.00 s to 600.00 s 0 = Timed Out |
Initial Timeout |
Internal Parameter, Read-write, Analog (unsigned 16-bit integer) 0.01 s to 600.00 s |
Timeout |
Internal Parameter, Read-write, Analog (unsigned 16-bit integer) 0.01 s to 600.00 s |
Output |
Output, Read-only, Boolean (signed 16-bit integer) 0 = OK 1 = Alarm |